Propane in cold weather: will your tank keep a generator running?
A propane tank holds liquid. Your generator burns vapor. The liquid has to boil off inside the tank first, and it takes its heat from the outside air through the tank wall. Two things slow that down: cold air and a low tank, because less liquid touches less steel.
When the tank cannot make vapor as fast as the engine burns it, pressure drops and the generator stumbles or shuts down, often with fuel still in the tank. It tends to happen at the worst moment: a long outage, deep cold and a tank that has been drawn down for days.
How much vapor a tank can supply
The propane industry's rule of thumb multiplies the tank's diameter by its length and by a factor for how full it is, then scales the result for temperature. These figures are for a tank that is 30% full.
| Tank | 40°F (4°C) | 20°F (-7°C) | 0°F (-18°C) | -10°F (-23°C) | -15°F (-26°C) |
|---|---|---|---|---|---|
| 120 gallon tank | 228,000 | 228,000 | 114,000 | 57,000 | 29,000 |
| 250 gallon tank | 395,000 | 395,000 | 197,000 | 99,000 | 49,000 |
| 320 gallon tank | 483,000 | 483,000 | 242,000 | 121,000 | 60,000 |
| 500 gallon tank | 630,000 | 630,000 | 315,000 | 158,000 | 79,000 |
| 1,000 gallon tank | 1,102,000 | 1,102,000 | 551,000 | 276,000 | 138,000 |
BTU per hour. A tank at 60% full supplies about 40% more than these figures; at 10% full, about a third less.
How much a generator needs
| Generator | At a 3 kW household load | At full output | Smallest tank that keeps up at full output, 0°F and 30% full |
|---|---|---|---|
| 10 kW | 70,000 | 135,000 | 250 gallon tank |
| 14 kW | 100,000 | 267,000 | 500 gallon tank |
| 18 kW | 77,000 | 263,000 | 500 gallon tank |
| 22 kW | 135,000 | 339,000 | 1,000 gallon tank |
| 24 kW | 132,000 | 339,000 | 1,000 gallon tank |
| 26 kW | 77,000 | 361,000 | 1,000 gallon tank |
| 28 kW | 79,000 | 363,000 | 1,000 gallon tank |
BTU per hour, from the makers' published burn rates.
What to do about it
- Keep the tank above 30 to 40% through winter. Fuller tanks make more vapor. Ask your supplier for automatic delivery with a winter trigger.
- Size the tank for the generator, not just the furnace. A fireplace or range needs a fraction of what a standby generator burns. If you are adding a generator to an existing small tank, check the table above first.
- Two tanks beat one. Tanks joined together double the surface that makes vapor as well as the fuel.
- Keep snow and ice off the tank and regulator. A buried tank cannot draw heat from the air.
- Never warm a tank with a flame or heater. If pressure is the problem, the fix is more tank, not more heat.
The propane runtime calculator runs this check for your own tank, fill level and temperature.
See what this means for your own home and fuel.
Open the planner