How we calculate
Every number on this site comes from the formulas on this page. Where a manufacturer or industry body publishes a figure, we use it and say so. Where we estimate, we say that too. Data last reviewed November 25, 2026.
1. Your load
- Running load is the sum of running watts for everything switched on. With "big appliances take turns" on, we count all ordinary items, plus the single largest 240-volt appliance and the single largest short-use kitchen or laundry appliance. That reflects how a load-management module and ordinary habits keep them from overlapping.
- Starting peak is the running load plus the largest extra start-up surge among the items counted. Motors rarely start in the same instant.
- Energy per day is running watts times typical hours of running for each item. You can replace it with a figure from your own utility bill or battery app.
- Generator size is the running load plus 20% headroom, and the generator's surge rating must cover the starting peak. Standby units are credited with 25% surge above their rating.
Appliance figures are typical values from generator makers' wattage worksheets. The nameplate on your own appliance is always the better number.
2. Standby generator fuel
Makers publish fuel burn at half load and at full load only. We use Generac's published air-cooled figures as the reference, because it publishes them for every size:
| Size | Series | Propane, half load | Propane, full load | Natural gas, half | Natural gas, full | Rating on gas |
|---|---|---|---|---|---|---|
| 10 kW | Guardian | 0.97 gal/h | 1.48 gal/h | 101 ft³/h | 127 ft³/h | 9 kW |
| 14 kW | Next Generation | 1.76 gal/h | 2.92 gal/h | 189 ft³/h | 243 ft³/h | 14 kW |
| 18 kW | Next Generation | 1.65 gal/h | 2.87 gal/h | 164 ft³/h | 235 ft³/h | 17 kW |
| 22 kW | Next Generation | 2.45 gal/h | 3.71 gal/h | 221 ft³/h | 311 ft³/h | 21 kW |
| 24 kW | Next Generation | 2.45 gal/h | 3.71 gal/h | 197 ft³/h | 291 ft³/h | 21 kW |
| 26 kW | Next Generation | 2.05 gal/h | 3.95 gal/h | 182 ft³/h | 316 ft³/h | 22.5 kW |
| 28 kW | Next Generation | 2.23 gal/h | 3.97 gal/h | 182 ft³/h | 297 ft³/h | 25 kW (approx.) |
Between half and full load we draw a straight line through the two published points. Below half load, where homes spend most of an outage, we draw a line from the half-load point down to a no-load burn. That no-load burn is the straight-line extension of the published points, held between 12% and 30% of the full-load rate, the range small spark-ignited generator sets fall in. Because nobody publishes these low-load figures, we show a range of plus or minus 15% below half load and 8% above it.
3. Portable generator fuel
Portable makers publish a run time at half load. From popular 7,500 and 9,500 watt dual-fuel models we derive: full-load gasoline burn of 0.148 gallons an hour per rated kW, a no-load burn of 35% of that for conventional open-frame units and 20% for inverter units, and a straight line between. On propane the same engine burns 1.25 times the volume, because a gallon of propane holds less energy, and delivers about 90% of its gasoline rating. Our tests check the result against published run times for Champion and Honda models.
A portable is assumed to run a set number of hours a day, 16 unless you change it, and your appliances draw only while it runs. Standby units are assumed to run around the clock.
4. Propane tanks
- Tanks are filled to 80% of their volume. We stop counting fuel at 10% for tanks, and at empty for cylinders.
- Propane holds 91,502 BTU per gallon.
- Cold-weather check. A tank can only feed a generator as fast as its liquid boils off. We use the propane industry rule: vapor capacity in BTU per hour at 0°F equals tank diameter times length (in inches) times a factor that runs from 45 at 10% full to 100 at 60% full. The result is scaled for temperature: a quarter of that at -15°F, half at -10°F, double at 20°F and above. If your tank cannot keep up with the generator at your average load, we stop counting fuel at the fill level where it falls behind.
| Tank | Diameter | Length | Vapor at 0°F, 30% full |
|---|---|---|---|
| 120 gallon tank | 24 in | 68 in | 114,240 BTU/h |
| 250 gallon tank | 30 in | 94 in | 197,400 BTU/h |
| 320 gallon tank | 30 in | 115 in | 241,500 BTU/h |
| 500 gallon tank | 37.5 in | 120 in | 315,000 BTU/h |
| 1,000 gallon tank | 41 in | 192 in | 551,040 BTU/h |
Dimensions vary by manufacturer. These are representative.
5. Batteries and solar
- Portable power stations deliver 88% of their rated capacity to your appliances after inverter losses, and can surge to 2 times their rated output for motor starts.
- An installed home battery is modeled as 13.5 kWh and 10 kW per unit with 95% delivered, up to 4 units.
- Rooftop solar is counted only with a home battery, because grid-tied solar shuts off in an outage without one. Daily output is array size times 2.5 sun-hours in freezing weather or 5 otherwise, times 0.75 for system losses.
6. Prices
Equipment prices are typical late-2026 ranges for the United States; Canadian figures are converted at 1.38 and rounded. Default fuel prices: United States, propane $2.82 a gallon, gasoline $3.90 a gallon, natural gas $1.60 a therm. Canada, propane $1.10 a litre, gasoline $1.55 a litre, natural gas $0.50 a cubic metre. Propane: EIA weekly residential survey, week of Nov 16, 2026. Gasoline: AAA national average, Nov 12, 2026. Natural gas: typical residential rate. Gasoline: Kalibrate national average, Nov 23, 2026. Propane and natural gas: typical delivered residential rates; check your own bill.
7. What the planner leaves out
- Generators lose output at high altitude and in extreme heat. We do not derate for either.
- Natural gas supply pressure and meter capacity. We show the BTU per hour your meter must deliver; your utility confirms whether it can.
- Electrical code load calculations. An installer's calculation under your local code governs the final size.
- Battery self-consumption while idle, and reduced battery output in deep cold.
- Differences between brands. Other makers' standby units burn within a similar range; check your model's spec sheet.
Sources
- Generac Power Systems, How Much Fuel Does My Home Standby Generator Use? Air-cooled fuel consumption tables.
- RegO Products, field topic "Determining Propane Vapor Capacity": the diameter times length times K rule, fill factors and representative tank dimensions.
- Propane Education & Research Council, technical pocket guide: energy content of propane and natural gas.
- LP-Gas Serviceman's Manual: vaporization rates for 100 lb cylinders and temperature multipliers.
- Champion Power Equipment, Generac, Westinghouse and Honda product specifications: portable generator run times.
- U.S. Energy Information Administration, Weekly Heating Oil and Propane Survey; AAA and Kalibrate fuel price reports.
- U.S. Consumer Product Safety Commission: generator placement and carbon monoxide guidance.